Cette consultation a eu lieu :
du 27 mai 2020
au 26 juin 2020
Résumé de la proposition
7-Eleven Canada, Inc. wants an extension to May 31, 2022, to remove single-wall steel underground piping. The piping failed a Cathodic Protection test (i.e. pipe is not protected from corrosion) in February 2020 but passed a precision leak test in April 2020.
Détails de l'emplacement
Adresse du site
366 CHRISTINA ST N
SARNIA,
ON
N7T 5V7
Canada
Détails de l'emplacement du site
gas station
Carte de l'emplacement du site
L'épingle de localisation correspond à la zone approximative où a lieu l’activité environnementale.
Afficher cet emplacement sur une carte opens link in a new windowPromoteur(s)
7-ELEVEN CANADA INC - NATIONAL GAS DEPT
3200 HACKBERRY RD
IRVING ,
TX
75063
États-Unis
Détails de la proposition
Clause 2.3.1.4 of the Liquid Fuels Handling Code (LFHC) allows single-wall underground pipe to remain in place within 12 months of failing a Cathodic Protection test, provided the pipe passes a precision leak test.
7-Eleven is planning to do a full tank/line replacement in 2022 at the site. Without this variance to keep the piping in place until 2022, 7-Eleven would have to close the store, leaving staff unemployed.
7-Eleven monitors the site’s environmental stability using:
- an automatic tank gauge (Veeder-root TLS 350R) for inventory
- alarm management through stand-alone sensors
- Continuous Statistical Leak Detection (CSLD) at the tanks
- electronic pressurized line leak detection (PLLD) on the product piping
7-Eleven monitors these results monthly and ensures the required testing, in accordance with LFHC 2017, Section 4.6.9 (shear valves and electronic detection system), is completed annually by Dart Petroleum Services.
In addition, 7-Eleven arranges for a certified third party testing organization, Cantest, to inspect the operation of the stand-alone sensors and PLLD on an annual basis. Cantest also carries out precision testing every two years.
If this variance is accepted, 7-Eleven will increase the frequency of the precision testing of the product lines.
Documents justificatifs
Consulter les documents en personne
Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.
Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.
Commentaire
La consultation est maintenant terminée.
La période de consultation a eu lieu du 27 mai 2020
au 26 juin 2020